HYDAC pressure transmitter Digital Display Unit HDA 5500
Description:
The Digital Display Unit HDA 5500 is a microprocessor controlled display and monitoring unit designed for control panel mounting. Different versions are available with a maximum of 3 analogue inputs and 4 relay outputs. The analogue input signals are displayed according to the measuring scale selected by the user. Each of the 4 relay outputs can be allocated to each of the 1 to 3 sensor
inputs or to the differential between input 1 and 2. The PT100 temperature probe can be connected directly to the unit. There is
also an option for frequency measurement using the HDS 1000 (HYDAC rpm probe), for example, to measure the speed of rotating
components. The analogue output is standard and adjustable for 4 to 20 mA or 0 to 10 V.
Special features:Digital display of analogue signalsClear 4 digit 7 segment LED displayUp to 3 analogue inputs
(4 .. 20 mA, 0 .. 10 V or 0 .. 5 V)Accuracy !à 0.5 Differential measurement possibleUp to 4 relay outputsRS 232 serial interfaceSupply 12 to 32 VDC or 85 to 265 VAC 50 / 60 HzOption with PT100 sensor input or frequency input.
Technical specifications:
Display range
Display4-digit 7-segment LED-display, red,
height of digits 14.2 mm
3 LEDs for active sensor
4 LEDs for switch points
Display range-999 .. 9999 (adjustable by user)
Display units withbar, kg/cm2, Mpa, psi, !aC, !aF, l/min, mA, V, Hz, k
background lightingm, mm, inch, l, l/min, gal, gal/min, 1/min, %, t
Input data
Analogue signal input(s)
Measuring range(s)adjustable: 4 .. 20 mA, 0 .. 5 V or 0 .. 10 V
(up to 3 analogue inputs)
Accuracy class !à 0.5 % at 25 !
PT 100 - Input
Measuring range- 25 .. 100 !a
Accuracy class !à 0.5 % at 25 !
Frequency-/counter input
Signal threshold0 .. 0.6 V = LOW, 3 .. 24 V = HIGH
Frequency range15 Hz to 4 kHZ
Output data
Analogue outputadjustable:4 .. 20 mA, Ohmic resistance 400 or
0 .. 10 V, Ohmic resistance 2 k
Accuracy of the analogue output !à 0.5 % at 25 !
Rise time70 ms
Switching outputs
Type2 or 4 relays each with separate common supply
Switching voltage0.1 .. 250 VAC
Switching current9 mA .. 2 A
Switching capacity400 VA, 50 W
(for inductive loads use varistors)
Life expectancy of the 20 million at minimum load
switching contacts 1 million at nominal load
Reaction timeApprox. 20 ms
(with switching delay = 0 ms)
Setting range of the switching1.5 .. 100 % of the pre-set display range
points
Setting range of the switching0.5 .. 99 % of the pre-set display range
hystereses (switch-back points)
InterfaceSerial interface RS232
Baud rate 19200 Bauds - 8 data bits -
1 start and stop bit - no parity, no handshake
Ambient conditions
Nominal temperature range0 .. + 50 !a
Operating temperature range0 .. + 50 !a
Storage temperature range- 40 .. + 80 !a
- marksEN 50081-1 and -2, EN 50082-1, EN 61000-6-2
Other data
HousingControl panel housing 96 x 48 x 109 mm
Control panel cut-out 92 (+0.8) x 45 (+0.6) mm
Front panel thickness 1.25 .. 15 mm
Maximum installation depth 121 mm
Electrical connections Supply voltage: plug-in terminal block, 2 pole, RM 5.08
Input/Outputs: plug-in terminal block, 11 pole, RM 3.5
Relay: plug-in terminal block 6 pole, RM 5.08
Max. cross-section of the connections 1.5 mm2 for
input/outputs
Max. cross-section of the connections 2.5 mm2 for
supply voltage and relays
Supply voltage85 .. 265 VAC 50 / 60 Hz or 12 .. 32 VDC
Power consumption15 VA at 85 .. 230 VAC ¨C Fuse protection 1 A
Supply of the measurement
transmitter12 !à 1 % VDC max. 20 mA per analogue inpu
Protection class to DIN 40050IP 20
Reverse polarity protection of the provided
supply voltage, excess voltage,
override protection
Weightapprox. 320 g