Gems Fluid Level Sensors & Control Switches warrick conductivity sensors
Warrick® Conductivity liquid level control systems rely on the liquid level sensing capability of probes (electrodes) that are housed inside fittings designed to accommodate one or more probes. The concept is simple: take advantage of a liquid’s conductive properties to complete a circuit and cause a control relay to actuate. These single- or multi-point sensors have no moving parts and the stainless steel corrosion-resistant electrodes can be cut to the desired length. Multiple probes per fitting allow control of several functions in less space with less expense for equipment and installation. To create a system select from numerous level controllers, fittings and probe options. For OEM’s we also have the capability to custom configure liquid level control units and electrode fittings to meet your specific level control application requirements.
C-700 Series Low Level Cut Off Control
Internal Mounting
Meets CSD1 Requirements
U.L. Recognized "Limit Control"
Compact Size
Options Include: Manual Reset, Power Outage Feature, and Test Feature
LWC-720 Series Low Level Cut Off with Pump Control
Internal Mounting
Includes Pump Control Switch, Logic and Relay
Meets CSD1 Requirements
U.L. Recognized "Limit Control"
Compact Size
Options Include: Manual Reset, Power Outage Feature, and Test Feature
LWC-800 Series Low Level Cut Off Control
External Mounting
Meets CSD1 Requirements
U.L. Recognized "Limit Control"
Compact Size
Options Include: Manual Reset, Power Outage Feature, and Test Feature
Series M-Mechanical Tilt Float Level Switch Non-Mercury Switch Sealed Cable Impact & Corrosion Resistant ABS Shell N.O., N.C., SPDT Contacts Various Cable Lengths Color Coded Body. Designed for level control and alarm applications in dificult liquids such as sewage and waste water. Series M mechanical tilt loats are ideal for applications where the presence of mercury is a concern. Series M, Switches have impact resistant ABS shell and neoprene jacketed cable.
Speciications
Cord 2 or 3 conductor 16 AWG wire SJOW Oil Resistant CPE
Contact Rating 13 amp @ 120/240 VAC 1/2 hp
Contact Design SPST, Normally Open or Normally Closed
Common with N.O. & N.C. (form C)
Temperature Rating
Dry 32!aF to 194!aF (0!aC to 90
Water Resistant 32!aF to 140!aF (0!aC to 60
Overall Weight 1.0 lbs. (not including weight)
Tether Method Tie-wrap nylon, weight: 2.5 lbs.
Approvals U.L. Recognized, CSA Cert.
Applications
Level Control
Alarms
Sewage Lift Systems
Slurries
Drainage Sumps
Wastewater Treatement
Holding Tanks
Warrick Control Panels
Warrick Alarm Panels
Kits and Options
Series CP
Control Panel Standard Level Control System Electrical Panel
Model
CP16
Supply Voltage
120 VAC
Panel Function
Simplex Pump Down
Control Sensitivity
50 K
Mode of Operation
Inverse
Enclosure
NEMA 4X
Alarm Options
Audible/Visual Contacts
Contact Design
SPST
Contact Rating
10 Amp
Minimum Temperature (°F)
-40
Warrick® Liquid Level Sensors are available in single- and multi-probe models with a variety of fittings. The versatility of the Warrick® design makes these sensors ideal for a diverse range of applications.
Examples include:
Food and Beverage
Caustics and Acids
Sumps
Reservoirs
Pharmaceuticals
Boilers and Steam Generators
Ponds
Sewage and Wastewater
Probe Styles
Metal Rods
Wire Suspended
Corrosion Resistant
Sanitary
Fitting Styles
3/8" to 3" Threaded Mount
Bracket Mount
Flange Mount
External Mount
Sanitary Mount
Condulet Mount
Series 3B Two-Piece threaded Coupling
Model
3B
Number of Probes
1
Body Material
316 Stainless Steel
Probe Length
N/A
Mounting
3/8"-18 NPT
Gauge Tappings
N/A
Tricock Tappings
N/A
Probe Type
N/A
Probe Material
N/A
Sheathing Material
N/A
Pressure Rating
400 psig @ 406 F
Maximum Temperature (°F)
N/A
Approvals
Ul, CSA, FM
Minimum Qty (per Releas
For over 50 years Warrick® Controls have offered dependable no-moving-parts control and monitoring of conductive liquids. Now as part of the Gems™ Sensors family, Warrick® conductivity controls continue to offer reliability, process automation, labor savings, flexibility and operator safety at economical cost. The concept is simple: take advantage of a liquid’s conductive properties to complete a circuit and cause a control relay to actuate. Use of permanently-mounted stationary electrodes gives the user precise accuracy, repeatability and no-moving-parts reliability. This simple concept has led to the development of a complete line of conductivity-based liquid level detectors and control units and electrode fittings shown here. For OEM’s we also have the capability to custom configure liquid level control units and electrode fittings to meet your specific application requirements.
System Components
The liquid level control unit is an electrical device with contacts that open and close in response to liquid levels sensed by the probes. Because it is wired directly to the power source and to the sensing source, it can send signals that activate or de-activate solenoids, pu