Fischer pressure transmitter Building technology Differential Pressure Gauge - Low Range - Air, Gases-DA08
Gas Alarm offer Fischer Germany differential pressure gauge DA08. These instruments are mainly used in industrial and climatic engineering to measure low and lowest differential pressures. They are suitable for measuring non-aggressive and clean gaseous media.
Main Features:
- For small ranges (4 mbar and higher)
- Simple technical construction
- Maintenance-free
- Typical Applications:
- Moving tap filters
- Ventilators
- Veturitubes
- Air flow application
- gas application
- Specifications:
- Measuring range: 0-4 mbar up to 0-160 mbar (see Ordering Code)
- Max. overpressure: For ranges ≤ 16mbar 10x FS; For ranges > 16mbar max. 200 mbar
- Max. stat. operating pressure: 200 mbar
- Accuracy: Class 1.6 acc. to DIN 16005
- Perm. ambient temperature: -20 to +70°C
- Max. media temperature: Max. 50°C
- Indicator: Circular dial type ø 100 or 160 mm, 270°-scale
- Pressure connections: At the bottom or rear of the housing
- Zero point adjustment: Located in the dial
- Housing: Aluminium varnished black
- Capsule element: CuBe2
- Front glass: Plexiglass