Kaneko manual reset solenoid valve
In the solenoid valve is used for emergency solenoid valve and Maniaru reset operation is performed for the power outage, automatically switches the solenoid valve typically Maniaru expression Operating reset once again. or energized, even if the power failure, unless manually reset is semi-automatic valve with a mechanism that does not change the operating position.
M31 SERIES
Feature
Can be used even with a pressure differential of zero as main and pilot valves are directly connected to each other.
Pressure losses are small as nominal size is equal to seat size.
Products certified for high-pressure gas services are also available.
Designed so that the valve after once actuated does not change its state unless it is manually reset.
Precautions
Install the valve with the solenoid upward with respect to horizontal piping (permissible angle of inclination is within 30 degrees to the vertical).
Limited flow directions (align with the arrow indicating the flow direction).
Limited flow directions (align with the arrow indicating the flow direction).
Remove air through vent valve in cases where the working fluid is a liquid.
Do not paint external moving parts.
Standard specification
FLUID
GAS , LIQUID , STEAM
WORKING PRESSURE
See below
FLUID TEMPERATURE
As for working temperature you can select any KANEKO model no. that will have different inner construction. The using temperature is available form 5deg.C to 200deg.C.
AMBIENT TEMPERATURE
-20℃ ~ 40℃(But to be used within the range of fluid dose not f
M51 SERIES
Feature
A kind of safety valve capable of preventing malfunctioning.
Being a semi-automatic type, the valve does not operate freely like an ordinary solenoid valve by turning on or off of the power.
Packed type
Free from any fear of burnout or insulation degradation as the coil and movable core do not come into contact with fluid.
Easy to operate manually.
You can just press the palm ratchet button.
We offer two types of operation and with the operation when the power during a power outage.
Standard specification
FLUID
CLEAN AIR
FLUID TEMPERATURE
-20 ~ 60℃
AMBIENT TEMPERATURE
-20 ~ 60℃
DUTY CYCLE
100% CONTINUOUSLY RATED
OPERATING VOLTAGE RANGE
+10,-15%
WORKING PRESSURE
0 ~ 0.99MPa
Cv. FLOW FACTOR
0.58
ELECTRICAL SPECIFICATIONS
See below
ELECTRICAL SPECIFICATIONS
AC
DC
V/Hz
INRUSH A
HOLDING A
V
A
COIL INSULATION CLASS : B
100/50
2.8
0.50
24
0.91
100/60
3.1
0.56
48
0.53
110/60
2.6
0.46
100
0.24
200/50
1.4
0.25
1
M81 SERIES
Feature
A kind of safety valve capable of preventing malfunctioning.
Being a semi-automatic type, the valve does not operate freely like an ordinary solenoid valve by turning on or off of the power.
Packed type
Free from any fear of burnout or insulation degradation as the coil and movable core do not come into contact with fluid.
Easy to operate manually.
Can be latched with the push of the palm button. Available in two types ― no voltage release and electrically tripped.
Standard specification
FLUID
CLEAN AIR
FLUID TEMPERATURE
-20℃~60℃
AMBIENT TEMPERATURE
-20℃~60℃
DUTY CYCLE
100% CONTINUOUSLY RATED
OPERATING VOLTAGE RANGE
+10%,-15%
WORKING PRESSURE
0 ~ 0.99MPa
Cv. FLOW FACTOR
0.58
ELECTRICAL SPECIFICATIONS
See below
ELECTRICAL SPECIFICATIONS
AC
DC
V/Hz
INRUSH A
HOLDING A
V
A
COIL INSULATION CLASS : B
100/50
2.8
0.50
24
0.91
100/60
3.1
0.56
48
0.53
110/60
2.6
0.46
100
0.24
200/50
1.4
0.25
110
0.26
M55 SERIES
Feature
A kind of safety valve capable of preventing malfunctioning.
Being a semi-automatic type, the valve does not operate freely like an ordinary solenoid valve by turning on or off of the power.
Constant power consumption.
As a direct-acting, manual-reset type three-way valve is used as the pilot valve, power consumption is kept constant, irrespective of the valve size.
Packed type
Free from any fear of burnout or insulation degradation as the coil and movable core do not come into contact with fluid.
Easy to operate manually.
Can be latched with the push of the palm button.
Available in two types ― no voltage release and electrically tripped.
Standard specification
FLUID
CLEAN AIR
FLUID TEMPERATURE
-20 ~ 60℃
AMBIENT TEMPERATURE
-20 ~ 60℃
DUTY CYCLE
100% CONTINUOUSLY RATED
OPERATING VOLTAGE RANGE
+10,-15%
WORKING PRESSURE
0.12 ~ 0.99MPa
Cv. FLOW FACTOR
See below
ELECTRICAL SPECIFICATIONS
See below
Cv. FLOW FACTOR
NOMINAL DIAMETER
8
10
15
20
25
32
Cv. FLOW FACTOR
1.22
3.2
4.3
5.18
14.5
17.3
ELECTRICAL