Honeywell Solenoid valves for hot water, steam, up to 120 degree LG-series Flange connection L25G31F
Fema piston-type solenoid valves of the LG series are particularly suitable for use as stop and safety check valves in heating installations
up to 120°C or 180°C.
The coupled (automatically servo-controlled) mode of operation does not require a minimum differential pressure; the units open and close
without difficulty even without pressure or with low differential pressures.
DN size mm: 25
Kvs value: 10
Static pressure: N40
Working range bar: 0…20
Connections: flange
Technical data
Type: 2/2-way
Operating mode: normally closed
Type of construction: Piston-type solenoid valve, coupled,, no minimum differential pressure required, TÜV-tested to DIN 32730, Type test approval mark (DIN reg. no.) see Product Summary
Materials: Casing: Bronze Rg 5 to DIN 1705
Internal parts: Brass (CuZn40Pb) and corrosion-resistant steel
Sealing materials: Piston: Teflon (PTFE).
Nozzle: Cone made of stainless steel.
Static seal: EPDM
Mounting position: Standard version: Solenoid system preferably upright. Horizontal mounting position possible for DN 15 to DN 32. For DN 40 and 50 a horizontal mounting position is not permitted. The solenoid system should not hang downwards.
Outdoor installations fr = suitable for outdoor use
Ambient temperature: 4°C to +60°C
Temperature of medium: 120°C/180°C maximum
Working pressure: See Product Summary
Flanges
To DIN 2501 Part 1
PN 40 for DN 15–32
PN 25 for DN 40/50
Recommended weld-on flange
PN 40 to DIN 2635
Maintenance
The valve should be operated 5-10 times per month to prevent
the piston from sticking. No further maintenance is required.