JUMO pressure transmitter
JUMO is one of the leading manufacturers in the field of industrial sensor and automation technology. Our innovative product range includes the entire measuring chain from sensors to automation solutions for temperature, pressure, liquid analysis, flow rate, filling level, and humidity.
JUMO always aims to provide our customers with the optimal solution for process reliability, energy efficiency and cost optimization.
Features
Measuring ranges: 0 to 250 mbar up to 0 to 600 bar relative pressure, 0 to 1 bar up to 0 to 25 bar absolute pressure
Linearized and temperature-compensated measuring range
Measuring principle: piezoresistive or thin-film (strain gauge)
Stainless steel measuring cell, fully welded
Temperature of medium: -40 to +125 °C
Optional high-temperature version up to 200 °C (SIP and CIP compatible)
Measured values transmitted in any units to the CANopen bus
Protection type: IP67
Customer benefits
Robust to withstand high mechanical loads
Excellent process reliability is guaranteed by the combination of protection type IP67, a high level of vibration resistance, parts in contact with media that are made of stainless steel, and a front flush, welded system.
Compact and economical
The small dimensions (Ø 27 mm × 65 mm) allow a flexible installation position with simple wiring and assembly, while optimizing use of materials. Uniform parameterization and diagnosis of the entire CAN bus system down to the sensor level results in savings during startup and maintenance.
&n
Features
Measuring ranges: 0 to 1.6 bar up to 0 to 100 bar relative pressure
Linearized and temperature-compensated measuring ranges
Measuring principle: aluminum oxide ceramic thick-film sensor
Elastomer-sealed
Temperature of medium: -20 to +85 °C
Measured values transmitted in any units to the CANopen bus
Protection type: IP67
Customer benefits
Robust to withstand high mechanical loads
Excellent process reliability is guaranteed by the combination of protection type IP67, a high level of vibration resistance, parts in contact with media that are made of stainless steel, and a front flush, welded system. The capacitive ceramic measuring cell made from aluminum oxide (99.9 %) has long-term stability and a high level of overload protection.
Compact and economical
The small dimensions (Ø 27 mm × 65 mm) allow a flexible installation position with simple wiring and assembly, while optimizing use of materials. Uniform parameterization and diagnosis of the entire CAN bus system down to the sensor level results in savings during startup and maintenance.
Process reliability
Redundant
Features
Measuring ranges: 0 to 250 mbar up to 0 to 400 bar relative pressure, 0 to 600 mbar up to 0 to 25 bar absolute pressure
Linearized and temperature-compensated measuring ranges
Measuring principle: piezoresistive or thin-film (strain gauge)
Stainless steel measuring cell, fully welded (no seals)
Integrated temperature sensor: PT1000
Temperature of medium: -50 to +125 °C
Measured values transmitted in any units to the CANopen bus
Protection type: IP67
Customer benefits
Robust to withstand high mechanical loads
Excellent process reliability is guaranteed by the combination of protection type IP67, a high level of vibration resistance, parts in contact with media that are made of stainless steel, and a front flush, welded system. The stainless steel measuring cell is safe and reliable due to its long-term stability and high overload resistance.
Compact and economical
The small dimensions (Ø 27 mm × 65 mm) allow a flexible installation position with simple wiring and assembly, while optimizing use of materials. Uniform parameterization and diagnosis of the entire CAN bus system
Features
0 – 160 bar to 0 – 600 bar relative
Measuring range scaling 1:4
Process-reliability accuracy from 0.15 % of the nominal-value range setpoint value
Analog output can be freely configured by the user
Time-saving and simple configuration on the device or with easy-to-use setup program
Large, vibrant display
Flexible installation position through display (180°) rotation and subsequent auto-zero
Rotating case for better readability (+/-160°)
Product is not intended for export to the USA.
Customer benefits
Process reliability
The stainless steel sensor welded to the process connection has high bursting safety, equivalent in part to 5 times the measuring range. Consequently, the plant is reliably protected against medium leaks in the event of malfunction.
Uncomplicated and time-saving
The measuring device can be configured easily to save time, either on site or using an easy-to-use setup program.
Flexible
To optimize legibility, configuration, electrical installation, and the implementation of auto-zero, the case of the measuring device can be adjusted by +/-160° and the display by 180° in a user-friendly
Features
0 - 400 mbar to 0 - 60 bar relative / absolute
Measuring range scaling 1:4
Process-reliability accuracy as of 0.1 % of the nominal-value range end value
Analog output can be configured by the user
Time saving and simple configuration at the device or through a convenient setup program
Large, vibrant display
Flexible installation position through turning of the display (180°) and subsequent auto-zero
Turnable case for better readability (+/-160°)
Options available for high medium temperatures up to 200 °C (SIP and CIP compatible)
EHEDG-certified with JUMO PEKA process connection, type 409711 (hygienic design), made out of stainless steel
Customer benefits
Process reliability
A hygienic design, parts that are in contact with the media being made of stainless steel, and a cavity-free system prevent microbial contamination and therefore guarantee maximum process reliability for hygienic processes.
Uncomplicated and time-saving
The measuring device can be configured easily to save time, either on site or through a convenient setup program.
Flexible
To optimize legibility, configuration, electrical installation, and the implementatio
Features
Measuring ranges: up to 150mbar
Medium temperature: -15...+70 °C
Components coming into contact with the pressure medium are made of polycarbonate
Protection class: IP 54 IEC 529 (EN 60529), protection insulated
EC design test certificate
as per EC gas appliances directive
EC design test certificate
as per EC pressure equipment directive
TüV inspection as pressure monitors of a special
design as per TRD 604 and
VdTüV identification sheet Pressure 100/1, as well as
Class "S" as per EN 1854
Applications
Differential pressure monitoring in
Fuel technology
Ventilation technology
Air conditioning technology
Filter technology
Suitable for air, smoke and flue gas and other non-aggressive gasses
as a differential pressure monitor
Not suitable for technical combustion gasses
The differential pressure monitor of type 4 ADS-82 is suitable to switch a current circuit ON, OFF or change it over, when the actual pressure value changes in relation to the setpoint value.
The setpoint value (switching point) is manually set at a setting dial with scale. When the setpoint value is exceeded or fallen below, the current circuit is s
Features
Measuring ranges: -100 to +100 mbar up to -1 to +25 bar relative, 0 to 600 mbar to 0 to 25 bar absolute
For relative pressure, absolute pressure, and filling level
Impervious to aggressive and abrasive gases, vapors, and liquids
Temperature of medium: -40 to +120 °C
Linearity: ≤ 0.1 % of end value
Excellent long-term stability of < 0.1 % per year
Excellent temperature compensation
Operation on site or using HART protocol
Signaling if the measuring range is exceeded or not met and in the event of sensor exceedance and sensor faults
Visible on the display
Pressure in 13 different units; measured value in % or scaled with a choice of measuring unit
Output current in mA
Sensor temperature in °C or °F
Measured value error, measured value outside of measuring range
Minimum pressure and maximum pressure (drag indicator)
Pressure and sensor temperature can be displayed simultaneously
Settings via the operating keys
Zero point correction
Start and end of measuring without pressure specification (blind setting) or with pressure specification: simple, time-saving, conveni
Features
Measuring ranges: 0 - 60 mbar DP to 0 - 25 bar DP
For differential pressure, filling level, and flow
For non-aggressive and aggressive gases, vapors, and liquids
Temperature of medium: -40 to +100 °C
Linearity: ≤ 0.1 % of end value
Excellent long-term stability of < 0.1 % per year
Load on one and both sides up to a static pressure of 160 bar; up to 420 bar as an option
Excellent temperature compensation
Operation on site or using HART protocol
Signaling occurs if the measuring range is exceeded or not met; signaling also occurs in the event of sensor exceedance and sensor faults
Accessories: pressure separator, valves, setup program
ATEX approval available as an option
Display on the display
Pressure in 13 different units; measured value in % or scaled with a choice of measuring unit
Output current in mA
Sensor temperature in °C or °F
Measured value error, measured value outside of measuring range
Minimum pressure and maximum pressure (drag indicator)
Pressure and sensor temperature can be displayed simultaneously
Settings via the operating keys
Zero point correction
Start and end o
Features
Medium temperature: - 40... +200 °C (SIP and CIP compatible)
Possibility of local operation (keyboard/LCD) or operation through comfortable, digital communication (HART protocol)
LCD signals if the measuring range is exceeded or fallen below, measured value exceedance, probe defect
Fully welded measuring system
Accessories: seal, valves, setup program
Measuring ranges: 100 mbar... 600 bar
For relative pressure, absolute pressure and filling level
of non-aggressive and aggressive gas, vapors and liquids
High linearity: ≤ 0.1 % from standard value
High long-term stability: <0.1 % per year
Excellent temperature compensation
Optional with ATEX approval
Representation through display
Pressure in 13 different units; measured value in % or scaled with a freely selectable dimensional unit
Output current in mA
Sensor temperature in °C or °F
Measured value error, measured value outside of measuring range
Minimum pressure and maximum pressure (fly back)
Pressure and sensor temperature can be displayed simultaneously
Settings via the operating keys
Zero point correction
Start and end of the measuring process without
Features
HART® interface
Optional explosion protection Ex ia according to ATEX, INMETRO, GOST-R
Linearity: 0.05 %
Turn down: 1:50
Simple operation with rotary knob
Stainless steel case
Optional high-temperature version for up to 200 °C (SIP and CIP compatible)
EHEDG certified with JUMO PEKA process connection, type 409711 (hygienic design)
Setup program
LCD display with bar graph
Display scaling with a choice of measuring units
Display of sensor temperature
Display of minimum and maximum pressures
Current generator function
Customer benefits
Process reliability
Parts in contact with the medium are made of stainless steel (alternatively with NiMo alloy, or with a Monel, titanium or PTFE coating when used with a pressure separator). Combined with the front flush system, this offers optimum resistance to even aggressive media. The measuring instrument has a high degree of precision with deviation from characteristic line of 0.05 %, and offers excellent long-term stability of < 0.1 % per year. The version with explosion protection "Ex ia (intrinsically safe)" allows the pressure transmitter to be installed up to z
Features
HART® interface
Optional explosion protection Ex ia according to ATEX, INMETRO, GOST-R
Linearity: 0.07 %
Turn down: 1:200
Simple operation with rotary knob
Characteristic line and display also adjustable for flow measurement
Stainless steel case
Setup program
LCD display with bar graph
Display scaling with a choice of measuring units
Display of sensor temperature
Display of minimum and maximum pressures
Current generator function
Customer benefits
Process reliability
Parts exposed to the medium are made of stainless steel (alternatively with NiMo alloy, or with a Monel, titanium or PTFE coating when used with a pressure separator). This offers optimum resistance, even with aggressive media. The measuring instrument has a high degree of precision with deviation from characteristic line of 0.05 %, and offers excellent long-term stability of < 0.1 % per year. The version with explosion protection "Ex ia (intrinsically safe)" allows the pressure transmitter to be installed up to zone 0.
Simple and time-saving
The measuring instrument can be adjusted reliably and easily with a rotary knob on th
Features
HART® interface
Ex d explosion protection according to ATEX, INMETRO, GOST-R
Linearity: 0.07 %
Turn down: 1:200
Simple operation with rotary knob
Characteristic line and display also adjustable for flow measurement
Stainless steel case
Setup program
LCD display with bar graph
Display scaling with a choice of measuring units
Display of sensor temperature
Display of minimum and maximum pressures
Current generator function
Customer benefits
Process reliability
Parts exposed to the medium are made of stainless steel (alternatively with NiMo alloy, or with a Monel, titanium or PTFE coating when used with a pressure separator). This offers optimum resistance, even with aggressive media. The measuring instrument has a high degree of precision with deviation from characteristic line of 0.05 %, and offers excellent long-term stability of < 0.1 % per year. The version with explosion protection "Ex d (flameproof enclosure)" allows installation of the connection for zone 0 and the entire pressure transmitter in zone 1.
Simple and time-saving
The measuring instrument can be adjusted reliably and easily with a ro
Features
HART® interface
Ex d explosion protection according to ATEX, INMETRO, GOST-R
Linearity: 0.05 %
Turn down: 1:50
Simple operation with rotary knob
EHEDG certified with JUMO PEKA process connection, type 409711 (hygienic design)
Setup program
LCD display with bar graph
Display scaling with a choice of measuring units
Display of sensor temperature
Display of minimum and maximum pressures
Current generator function
Customer benefits
Process reliability
Parts in contact with the medium are made of stainless steel (alternatively with NiMo alloy, or with a Monel, titanium or PTFE coating when used with a pressure separator). Combined with the front flush system, this offers optimum resistance to even aggressive media. The measuring instrument has a high degree of precision with deviation from characteristic line of 0.05 %, and offers excellent long-term stability of < 0.1 % per year. The version with explosion protection "Ex d (flameproof enclosure)" allows installation of the connection for zone 0 and the entire pressure transmitter in zone 1.
Simple and time-saving
The measuring instrument can be adjusted reliab
Features
Measuring range: 0 - 250 mbar to 0 - 600 bar relative pressure, 0 - 600 mbar to 0 - 25 bar absolute pressure
Temperature of medium: -30 to +120 °C
For fluids and gas
All commercially available process connections, including hygienic
Fully welded stainless steel measuring system, without seals
Optional with increased linearity ≤ 0.2 % from end value
Protection type: IP65/IP67
Customer benefits
Process reliability
The fully-welded measuring system does not require seals and guarantees maximum process safety as well as reliability.
Its core is a piezoresistive measuring cell, featuring high overload resistance and longevity. It is safe, reliable, and temperature resistant.
Versatile
A broad spectrum of measuring ranges and electrical outputs as well as a large number of process connections guarantee variant diversity that can be specifically adapted to any application. Versions are available in a cast option and/or with reduced deviation from the characteristic line (≤ 0.2 % from end value). Protection types up to IP67 can be implemented with connecting cable or round plug if desired.
Applications
Industry
Food and
Features
Exclusively for dry, non-corrosive, and non-ionizing gaseous media
Measuring ranges: 0 to 40 mbar up to 0 to 600 mbar relative pressure
Protection type: IP65/IP67
Customer benefits
Process reliability
The transmitter is based around a piezoresistive measuring cell, which is safe and reliable with high overload resistance and long-term stability. This guarantees maximum process reliability thanks to its sensitive pressure recording of dry, non-corrosive, and non-ionizing gases.
Versatile
A broad spectrum of measuring ranges and electrical outputs as well as a large number of process connections that are not flush mounted guarantee variant diversity that can be specifically adjusted to any application with an appropriate specification.
Applications
Laboratory technology
Clean room technology
Compressed air control
The JUMO dTRANS p32 pressure transmitter with piezoresistive measuring cell is used to record relative pressures in dry, non-corrosive, and non-ionizing gaseous media. The nominal measuring ranges span from 0 to 40 mbar, to a maximum of 0 to 600 mbar as 2-wire or 3-wire versions. This sensitive pres